top of page

Description
Aux Cooling Water Pumps
The auxiliary cooling water pumps circulate water in a closed loop that serves as a method of cooling major equipment in the plant. The pumps are single stage centrifugal pumps sized for 50% of the design heat load but configured for all three to operate with variable speed drives that adjust speed to maintain a constant discharge pressure. If one pump is removed from service, the remaining two would increase speed to maintain the system at full capacity, thus adding redundancy to the system.
Specifications
Specifications
Number of Pumps: 3 ea.
Pump Size (HP): 200 HP
Coolant Flow Rate: 8,400 gpm
Material: Ductile Iron w/ 316SS Impeller
Vendors



Vendor Options
Detailed Design
Detailed Design Specifications

Video Explainer
Video Explainers
bottom of page