Â
Vacuum Pump
Two vacuum pumps are to be included with the ACC and sized to establish and/or maintain a vacuum on the turbine exhaust duct, ACC, and condensate receiver tank. A single pump would maintain a vacuum on the system during operation; however, both pumps operate at start-up to establish an operational ready status more quickly. The liquid ring vacuum pump option was selected instead of steam jet air ejectors to minimize water consumption.
Â
Specifications
Number of Vacuum Pumps: 2
System Pressure: 2 psia
System Flow Rate: 350 scfm
Operation: Continuous
Â



Vendor Options
Â
Detailed Design Specifications

Â